EasyManua.ls Logo

Daikin LXE10E-A - Page 152

Daikin LXE10E-A
238 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-10
Symptom Checkpoint RemedyCause
Stop of
evaporator fan
Faulty operation of suction
modulating valve SMV
Temperature
continues to
increase
Excessive frost
on evaporator
Opened discharge
gas bypass
solenoid valve BSV
(dusts caught in)
Excessive frost
on evaporator
Temperature
continues to
decrease
Disconnection of
fuse (Fu2) circuit
Faulty operation
of defrost solenoid
valve DSV
Replace the Fu2
Check operation of the DSV
Replace the DSV
The evaporator fan stops
Check the fan motor
Temperature continues
to decrease
Check for disconnection
in the Fu2 circuit
Is the DSV outlet
pipe cold?
Check the SMV
YES
YES
YES
NO
NO
NO
NO
YES
Is the opening of the
SMV 36% or more?
Is the BSV outlet
pipe hot?
Check operation of the BSV
Replace the BSV
YES
NO
Temperature continues
to increase
Manual defrost
As for the manual defrost, refer to page 2-23.
Piping
Removed or
loosen cramp
Auditory check
Visual check
Correct the cramp
Abnormal noise
Malfunction of
compressor inside
Auditory check Replace
Fan motor of
evaporator, condenser
Worn bearing
Auditory check Replace the unit
Interference with
fan guide
Auditory check
Visual check
Replace the faulty parts
Abnormal
vibration
Compressor, fan
motor
Loosen bolt
Auditory check
Visual check
Tighten bolts
Ⅴ Control is unstable (during chilled proportional control operation)
Ⅵ Abnormal noise or vibration
06LXE10E-A(1-27)07.2.233:11PMページ6-10
https://daikin-p.ru

Table of Contents

Related product manuals