Table 21 continued: MPS Standard Staging
Unit
Conguration
Compressor
Number
Circuit
Compressor
Model
MBH Stage 1 Stage 2 Stage 3 Stage 4 Stage 5
UnitType=2 Compressor State= 3 1 23 12 123
CoolingType=1 1 1 120 123 x x x
Comp Cong=D 3 1 090 93 x x x
Unit Size=030 2 2 090 93 x x x
37% 44% 67% 74% 100%
UnitType=2 Compressor State= 3 1 23 12 123
CoolingType=1 1 1 120 123 x x x
Comp Cong=D 3 1 090 93 x x x
Unit Size=035 2 2 120 123 x x x
34% 43% 69% 78% 100%
UnitType=2 Compressor State= 3 13 12 123
CoolingType=1 1 1 120 123 x x x
Comp Cong=3 3 1 120 123 x x x
Unit Size=040 2 2 120 123 x x
35% 68% 73% 100%
UnitType=2 Compressor State= 3 34 12 134 1234
CoolingType=1 1 1 120 x x x
Comp Cong=E 3 1 090 x x x x
Unit Size=040 2 2 120 x
4 2 090 x x x
26% 48% 63% 74% 100%
UnitType=2 Compressor State= 3 13 12 123 1234
CoolingType=1 1 1 120 123 x x x x
Comp Cong=E 3 1 120 123 x x x x
Unit Size=050 2 2 120 123 x x x
4 2 120 123 x
30% 52% 57% 81% 100%
CoolIng: MulTIsTage
www.DaikinApplied.com 37 IM 919-3 • MICROTECH III CONTROLLER