Table 22: Alternate Sequences (Dehumidication)
Unit
Conguration
Compressor
Number
Circuit
Compressor
Model
MBH Stage 1 Stage 2 Stage 3 Stage 4 Stage 5
UnitType=2 Compressor State= 1 12
CoolingType=1 1 1 083 x x
Comp Cong=4 2 2 068 x
Unit Size=015 54% 100%
UnitType=2 Compressor State= 3 1 12
CoolingType=1 1 1 083 x x
Comp Cong=D 3 1 041 x
Unit Size=015 2 2 068 x
30% 54% 100%
UnitType=2 Compressor State= 1 12
CoolingType=1 1 1 083 x x
Comp Cong=4 2 2 090 x
Unit Size=017 48% 100%
UnitType=2 Compressor State= 3 1 12
CoolingType=1 1 1 083 x x
Comp Cong=D 3 1 041 x
Unit Size=017 2 2 090 x
28% 48% 100%
UnitType=2 Compressor State= 1 13 123
CoolingType=1 1 1 068 x x x
Comp Cong=D 3 1 068 x x
Unit Size=020 2 2 083 x
35% 66% 100%
UnitType=2 Compressor State= 3 13 123
CoolingType=1 1 1 054 x x
Comp Cong=3 3 1 054 x x x
Unit Size=020 2 2 120 x
25% 46% 100%
UnitType=2 Compressor State= 1 13 123
CoolingType=1 1 1 068 x x x
Comp Cong=D 3 1 068 x x
Unit Size=025 2 2 120 x
30% 56% 100%
UnitType=2 Compressor State= 3 13 123
CoolingType=1 1 1 083 x x
Comp Cong=3 3 1 083 x x x
Unit Size=026 2 2 083 x
37% 63% 100%
UnitType=2 Compressor State= 3 1 13 123
CoolingType=1 1 1 120 123 x x x
Comp Cong=D 3 1 090 93 x x x
Unit Size=030 2 2 090 93 x
37% 44% 77% 100%
UnitType=2 Compressor State= 3 1 13 123
CoolingType=1 1 1 120 123 x x x
Comp Cong=D 3 1 090 93 x x x
Unit Size=035 2 2 120 123 x
34% 43% 73% 100%
UnitType=2 Compressor State= 3 13 123
CoolingType=1 1 1 120 123 x x
Comp Cong=3 3 1 120 123 x x x
Unit Size=040 2 2 120 123 x
35% 68% 100%
IM 919-3 • MICROTECH III CONTROLLER 38 www.DaikinApplied.com
CoolIng: MulTIsTage