Installation SV unit(s) is completed
SV units in seriesSV units in parallelOne SV unit
Choose airflow rate
AFR
out
>18.8 m³/h
Not allowed!
Determine other safety
measure.
Do NOT use external alarm safety measure in
the following cases:
1. SV unit installed in all other floors of a
building
2. SV unit installed in an occupied space
where people are restricted in their
movement
Connect an external alarm (field supply) to the
SVS output of the SV unit. This alarm must warn
audibly AND visibly and must be 15 dBA above
the background sound level at all times.
Determine total room area (= total area of the
space with natural ventilation and the space in
which the SV unit is installed).
The partition between two rooms on the same
floor MUST meet one of the two requirements
for natural ventilation.
Derive total refrigerant charge limit.
Alarm system must additionally
warn at a supervised location
with 24-hour monitoring.
Pressure inside the SV unit (P
internal
) must be
>20 Pa below the pressure of the surroundings.
Select a fan with the selected airflow and
calculated pressure capacity.
Make field settings in the SV unit accordingly
Install duct closing plate (accessory)
Install ductwork and extraction fan (both field supply) according to
the rules mentioned in the above text
Perform SV unit test run
YES
NO
Online access to
VRV Xpress?
NO
YES
Total charge amount
<
Total charge limit
YES
NO
Is one (or more) of the
three conditions met?
No safety measure
External alarm Natural ventilation
Ventilated enclosure
Is SV unit installed in occupancy:
1. with sleeping facilities?
2. where an uncontrolled number of people
are present?
3. accessible for persons not familiar with the
necessary safety precautions?
Install option EKBSDCK for
every connection to SV unit.
Use VRV Xpress to find the required
pressure capacity for selecting the correct
fan size.
A
1
+ A
min
[m²]
Total charge limit [kg]
See Step
1 in above text
See Step
2 in above text
See Step
4 in above text
§12.4.1 §12.4.2 §12.4.4§12.4.3