13 Unit installation
Installation and operation manual
24
SV1A25AJV1B+SV4~8A14AJV1B
VRV 5 safety valve unit
4P709466-1 – 2023.09
a
[mm]
c
485
c
485
d
500
b
720
(≥49.5)
291
f: 875 f: 450
A≥1800100
a
5
e e
g
e
[mm]
A Minimum distance to the floor
a Switch box
b Maintenance space
c Minimum connection space for refrigerant piping coming
from the outdoor unit, or for piping coming from or going
to another SV unit, drain piping and ducting
d Minimum connection space for the refrigerant piping to
the indoor units
e False ceiling
f False ceiling opening
g Floor surface
Ceiling strength. Check whether the ceiling is strong enough to
support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.
For existing ceilings, use anchors.
For new ceilings, use sunken inserts, sunken anchors or other
field supplied parts.
Ceiling openings. Respect the following sizes and positions for
the ceiling openings:
[mm]
450×450
A
40
30
100 100
875
A Ceiling opening size:
800mm (SV1~4A)
1200mm (SV6~8A)
13.2 Possible configurations
Refrigerant piping
A
B
C
b
1
a
a
1
a
a
b
2
b
2
b
A Refrigerant piping connected to left side only
B Refrigerant piping connected to right side only
C Refrigerant piping connected to both sides (flow-through)
1 From outdoor or from SV unit
2 From outdoor or from/to SV unit
a Stopper pipes (accessory)
b Field piping (field supply)
Ducting
A
a
1
A
a
a b
12
1
B
a
2
1
B’
a
a
b