14 Piping installation
Installation and operation manual
30
SV1A25AJV1B+SV4~8A14AJV1B
VRV 5 safety valve unit
4P709466-1 – 2023.09
PH2
SW8
1
3.2 N•m
2
2
4 Attach the damper wires.
Attach the damper wire on the refrigerant piping, in the
indicated places. Make sure the wire is tight, but do not pull
on it excessively.
Leave 20 cm of wire between the fixation on the pipe and
the entry into the switch box in order to be able to put back
the switch box.
Bundle the damper wire if needed.
SV1A
ba
bb
b
SV4A
ba
bb
b
SV6A
b
b
a
SV8A
b
b
a
a Damper wire
b Cable tie to fix damper wire to piping (field supply)
c Cable tie to bundle the damper wire (field supply)
d Leftmost wire fixing plate
To re-install the switch box
1 Lift the switch box, slide it backwards and lower it a short
distance.
2 Install and tighten the four screws. It is not required to tighten
the M8 bolts again.
SW8
3.2 N•m
3 Close the SV unit. See "13.3.3To close the unit"[425].
14 Piping installation
CAUTION
See "2 Specific installer safety instructions" [4 4] to make
sure this installation complies with all safety regulations.