Troubleshooting by Error Code SiUS331604E
187 Service Diagnosis
4.35 Transmission Error (Between Microcomputers on the
Outdoor Main PCB)
Error Code LC
Applicable
Models
All outdoor units
Method of Error
Detection
Transmission conditions between microcomputers on the outdoor main PCB are tested via
microcomputer.
Error Decision
Conditions
No normal transmission after a certain period of time
Supposed
Causes
Connection error between microcomputers on the outdoor main PCB
Defective outdoor main PCB (Transmission part)
Defective noise filter
External factors (Noise, etc.)
Defective inverter compressor
Defective fan motor
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
YES
NO
Replace the outdoor
main PCB.
Replace the inverter
compressor.
YES
YES
NO
NO
YES
Replace the fan motor.
No LC error. Check
the error code again.
NO
Is the outdoor
main PCB
damaged?
Inverter
compressor insulation
resistance is less than
100 k.
Fan motor
insulation resistance is
less than 1 M
.
Normal monitoring
light (green) of outdoor main
PCB (A1P) blinks.
YES
Replace the outdoor
main PCB.
Normal
monitoring light
(green) of inverter
PCB blinks.
(
)
Keep operating.
Possibly because of
sudden power failure, etc.
NO

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV IV-S RXTQ60TAVJU and is the answer not in the manual?

Daikin VRV IV-S RXTQ60TAVJU Specifications

General IconGeneral
CategoryHeat Pump
ModelRXTQ60TAVJU
Energy Efficiency Ratio (EER)3.48
RefrigerantR410A
Power Supply50 Hz
Operating Temperature (Heating)-15 to 20 °C

Related product manuals