SiUS331604E Troubleshooting by Error Code
Service Diagnosis 216
4.54 The Operation Lamp Blinks
Error Code -
Applicable
Models
ON/OFF controller
All indoor units
Method of Error
Detection
DIII-NET communication data is used to detect the error.
Error Decision
Conditions
-
Supposed
Causes
Defective transmission between the centralized controller and an indoor unit
Loosened setting connector of the master centralized controller
Defective ON/OFF controller PCB
Defective indoor unit PCB
Defective air conditioner
Troubleshooting
NO
YES
NO
NO
NO
YES
YES
Perform troubleshooting
using the Air Conditioner
Troubleshooting Manual.
Concurrently reset the
power supply of all the
centralized controllers.
Connect the power
supply of the indoor unit.
Correct the wiring.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Are
there any error
codes displayed on the
remote controller?
Is the
connection
wiring broken or
wrong?
Are any
connected
indoor units removed or
the control range
setting changed?
Is
the indoor
unit displaying
error connected to the
power supply?
YES
Go to the next page
A

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV IV-S RXTQ60TAVJU and is the answer not in the manual?

Daikin VRV IV-S RXTQ60TAVJU Specifications

General IconGeneral
CategoryHeat Pump
ModelRXTQ60TAVJU
Energy Efficiency Ratio (EER)3.48
RefrigerantR410A
Power Supply50 Hz
Operating Temperature (Heating)-15 to 20 °C

Related product manuals