SiUS331604E Troubleshooting by Error Code
Service Diagnosis 214
4.53 Address Duplication, Poor Setting
Error Code MC
Applicable
Models
Centralized controller
intelligent touch controller
Schedule timer
Method of Error
Detection
DIII-NET communication data is used to detect the error.
Error Decision
Conditions
Multiple centralized controllers or intelligent touch controllers are connected, and the controllers are
both set as master centralized controllers or slave centralized controllers.
Two schedule timers are connected.
Supposed
Causes
Centralized controller address duplication

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV IV-S RXTQ60TAVJU and is the answer not in the manual?

Daikin VRV IV-S RXTQ60TAVJU Specifications

General IconGeneral
CategoryHeat Pump
ModelRXTQ60TAVJU
Energy Efficiency Ratio (EER)3.48
RefrigerantR410A
Power Supply50 Hz
Operating Temperature (Heating)-15 to 20 °C