Outline of Control (Indoor Unit) SiUS331604E
53 Functions and Control
6.2 Set Temperature and Control Temperature
6.2.1 Without the Optional Infrared Floor Sensor
The relationship between remote controller set temperature and control target temperature is described below.
When the suction air thermistor is used for controlling (Default), the control target temperature is determined
as follows to prevent insufficient heating in heating operation.
Control target temperature: remote controller displayed temperature + 2°C (3.6°F).
The temperature difference for cooling heating mode switching is 5°C (9°F).
The above also applies to automatic operation.
When setting the suction air thermistor (Default setting)
When using the remote controller thermistor (Field setting is required)
Examples are given to illustrate a control target temperature that satisfies the remote controller set temperature.
Remote controller set temperature
Control target temperature
Remote controller set temperature
Control target temperature
˚C
Cooling
Heating
˚F
Temperature
Remote controller set temperature
Control target temperature
Remote controller set temperature
Control target temperature
˚C
Cooling
Heating
˚F
Temperature

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin VRV IV-S RXTQ60TAVJU and is the answer not in the manual?

Daikin VRV IV-S RXTQ60TAVJU Specifications

General IconGeneral
CategoryHeat Pump
ModelRXTQ60TAVJU
Energy Efficiency Ratio (EER)3.48
RefrigerantR410A
Power Supply50 Hz
Operating Temperature (Heating)-15 to 20 °C

Related product manuals