EasyManuals Logo

Danfoss AK-CH 650 User Manual

Danfoss AK-CH 650
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #64 background imageLoading...
Page #64 background image
64 Capacity controller RS8ER302 © Danfoss 2016-02 AK-CH 650
Set alarm priorities
1. Go to Conguration menu
2. Select Alarm priorities
3. Set priorities for Suction group
Press the +-button to go on to the next page
4. Set alarm priorities for condenser
Press the +-button to go on to the next page
Very many functions have an alarm connected.
Your choice of functions and settings has connected all the relevant
alarms that are current. They will be shown with text in the three
pictures.
All alarms that can occur can be set for a given order of priority:
• ”High” is the most important one
• ”Log only” has lowest priority
• ”Disconnected” gives no action
The interdependence between setting and action can be seen in the
table.
Conguration - continued
.
The rst alarms for the suction groups are shown here.
Further down in the display the priorities for the compressors’ safety
circuits are set.
In our example we select the settings shown here in the display
Setting
Log Alarm relays selection Net-
work
AKM-
dest.
Non High Low - High
High X X X X 1
Medium X X X 2
Low X X X 3
Log only X
Discon-
nected
See also alarm text

Table of Contents

Other manuals for Danfoss AK-CH 650

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss AK-CH 650 and is the answer not in the manual?

Danfoss AK-CH 650 Specifications

General IconGeneral
BrandDanfoss
ModelAK-CH 650
CategoryController
LanguageEnglish

Related product manuals