Non-UL compliance fuses
Frequency
converter
Max. fuse size Voltage Type
200-240 V - T2
1K1-1K5
16A
1
200-240 V type gG
2K2
25A
1
200-240 V type gG
3K0
25A
1
200-240 V type gG
3K7
35A
1
200-240 V type gG
5K5
50A
1
200-240 V type gG
7K5
63A
1
200-240 V type gG
11K
63A
1
200-240 V type gG
15K
80A
1
200-240 V type gG
18K5
125A
1
200-240 V type gG
22K
125A
1
200-240 V type gG
30K
160A
1
200-240 V type gG
37K
200A
1
200-240 V type aR
45K
250A
1
200-240 V type aR
380-480 V - T4
1K1-1K5
10A
1
380-500 V type gG
2K2-3K0
16A
1
380-500 V type gG
4K0-5K5
25A
1
380-500 V type gG
7K5
35A
1
380-500 V type gG
11K-15K
63A
1
380-500 V type gG
18K
63A
1
380-500 V type gG
22K
63A
1
380-500 V type gG
30K
80A
1
380-500 V type gG
37K
100A
1
380-500 V type gG
45K
125A
1
380-500 V type gG
55K
160A
1
380-500 V type gG
75K
250A
1
380-500 V type aR
90K
250A
1
380-500 V type aR
1) Max. fuses - see national/international regulations for selecting an applicable fuse size.
Table 4.3: Non-UL fuses 200 V to 480 V
If UL/cUL is not to be complied with, we recommend using the
following fuses, which will ensure compliance with EN50178:
Frequency Converter Voltage Type
P110 - P250 380 - 480 V type gG
P315 - P450 380 - 480 V type gR
Table 4.4: Compliance with EN50178
Electrical Installation
VLT
®
HVAC Drive Operating Instructions
MG.11.AD.02 - VLT
®
is a registered Danfoss trademark 23
4
4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 100 Series and is the answer not in the manual?

Danfoss FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelFC 100 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals