9-64 Device Identification
Range: Function:
0
*
[0 - 0 ] This parameter displays the device identification.
Please refer to the Instruction Manual for Profibus, MG.
33.CX.YY for further explanation.
9-65 Profile Number
Range: Function:
0 N/A
*
[0 - 0 N/A] This parameter contains the profile identifi-
cation. Byte 1 contains the profile number
and byte 2 the version number of the profile.
NOTE!
This parameter is not visible via LCP.
9-67 Control Word 1
Range: Function:
0
*
[0 - 65535 ] This parameter accepts the control word from a
Master Class 2 in the same format as PCD 1.
9-68 Status Word 1
Range: Function:
0
*
[0 - 65535 ] This parameter delivers the status word for a
Master Class 2 in the same format as PCD 2.
9-70 Programming Set-up
Option: Function:
Select the set-up to be edited.
[0] Factory setup Uses default data. This option can be used as
a data source to return the other set-ups to a
known state.
[1] Set-up 1 Edits Set-up 1.
[2] Set-up 2 Edits Set-up 2.
[3] Set-up 3 Edits Set-up 3.
[4] Set-up 4 Edits Set-up 4.
[9]
*
Active Set-up Follows the active set-up selected in
0-10 Active Set-up.
This parameter is unique to LCP and serial communication
busses. See also 0-11 Programming Set-up.
9-71 Profibus Save Data Values
Option: Function:
Parameter values changed via Profibus are not
automatically stored in non-volatile memory. Use
this parameter to activate a function that stores
parameter values in the EEPROM non-volatile
memory, so changed parameter values will be
retained at power-down.
[0]
*
Off Deactivates the non-volatile storage function.
[1] Store edit
setup
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to Off
[0] when all parameter values have been stored.
[2] Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to Off
[0] when all parameter values have been stored.
9-72 ProfibusDriveReset
Option: Function:
[0]
*
No action
[1] Power-on
reset
Resets the adjustable frequency drive upon
power-up, as for power-cycle.
[3] Comm option
reset
Resets the Profibus option only, useful after
changing certain settings in par. group 9-**,
e.g., 9-18 Node Address.
When reset, the adjustable frequency drive
disappears from the serial communication
bus, which may cause a communication error
from the master.
9-75 DO Identification
Range: Function:
0
*
[0 - 65535 ] Provides information about the DO (Drive
Object).
9-80 Defined Parameters (1)
Array [116]
No LCP access
Read only
Range: Function:
0 N/A
*
[0 - 9999 N/A] This parameter displays a list of all the
defined adjustable frequency drive
parameters available for Profibus.
Parameter Descriptions FC 300 Programming Guide
3-96 MG.33.MA.22 - VLT
®
is a registered Danfoss trademark
3
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 Series and is the answer not in the manual?

Danfoss FC 300 Series Specifications

General IconGeneral
CategoryDC Drives
EnclosureIP20
Communication OptionsCANopen
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Input Voltage380-500V AC

Related product manuals