EasyManuals Logo

Danfoss FC 300 Series User Manual

Danfoss FC 300 Series
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
3.3.9 1-9* Motor Temperature
1-90 Motor Thermal Protection
Option: Function:
The adjustable frequency drive determines the
motor temperature for motor protection in
three different ways:
Via a thermistor sensor connected to
one of the analog or digital inputs
(1-93 Thermistor Source). See section
PTC Thermistor Connection.
Via a KTY sensor connected to an
analog input (1-96 KTY Thermistor
Resource). See section KTY Sensor
Connection.
Via calculation (ETR = Electronic
Terminal Relay) of the thermal load,
based on the actual load and time.
The calculated thermal load is
compared with the rated motor
current I
M,N
and the rated motor
frequency f
M,N
. The calculations
estimate the need for a lower load at
lower speed due to less cooling from
the fan incorporated in the motor.
For the North American market: The ETR
functions provide class 20 motor overload
protection in accordance with NEC.
[0]
*
No
protection
Continuously overloaded motor, when no
warning or trip of the adjustable frequency
drive is required.
[1] Thermistor
warning
Activates a warning when the connected
thermistor or KTY sensor in the motor reacts in
the event of motor overtemperature.
[2] Thermistor
trip
Stops (trips) adjustable frequency drive when
connected thermistor or KTY sensor in the
motor reacts in the event of motor overtem-
perature.
The thermistor cut-out value must be > 3 kΩ.
Integrate a thermistor (PTC sensor) in the
motor for winding protection.
[3] ETR warning
1
Calculates the load when set-up 1 is active
and activates a warning on the display when
the motor is overloaded. Program a warning
signal via one of the digital outputs.
[4] ETR trip 1 Calculates the load when set-up 1 is active
and stops (trips) the adjustable frequency
drive when the motor is overloaded. Program
a warning signal via one of the digital outputs.
1-90 Motor Thermal Protection
Option: Function:
The signal appears in the event of a warning,
or if the adjustable frequency drive trips
(thermal warning).
[5] ETR warning
2
[6] ETR trip 2
[7] ETR warning
3
[8] ETR trip 3
[9] ETR warning
4
[10] ETR trip 4
Figure 3.4 ETR profile
1-91 Motor External Fan
Option: Function:
[0]
*
No No external fan is required, i.e. the motor is derated at
low speed.
[1] Yes Applies an external motor fan (external ventilation), so
that no derating of the motor is required at low speed.
The upper curve in graph above (fout = 1 x fM,N) is
followed if the motor current is lower than nominal
motor current (see 1-24 Motor Current). If the motor
current exceeds nominal current, the operation time still
decreases as if no fan were installed.
Parameter Descriptions FC 300 Programming Guide
3-24 MG.33.MA.22 - VLT
®
is a registered Danfoss trademark
3
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 Series and is the answer not in the manual?

Danfoss FC 300 Series Specifications

General IconGeneral
CategoryDC Drives
EnclosureIP20
Communication OptionsCANopen
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Input Voltage380-500V AC

Related product manuals