EasyManuals Logo
Home>Danfoss>DC Drives>FC 51 Series

Danfoss FC 51 Series User Manual

Danfoss FC 51 Series
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
4.2 Parameter Group 1: Load/Motor
1-00 Configuration Mode
Option: Function:
Use this parameter for selecting the
application control principle to be used when
a Remote Reference is active.
NOTE
Changing this parameter will reset 3-00
Reference Range, 3-02 Minimum Reference
and 3-03 Maximum Reference to their
default values.
NOTE
This parameter cannot be adjusted
while motor runs.
[0 ] * Speed
Open Loop
For normal speed control (References).
[3] Process
Closed
Loop
Enables process closed loop control. See
parameter group 7-3* Process PI Control for
further information on PI-controller.
1-01 Motor Control Principle
Option: Function:
[0] U/f Is used for parallel connected motors and/or special
motor applications. The U/f settings are set in 1-55
U/f Characteristic -U and 1-56 U/f Characteristic -F.
NOTE
When running U/f control slip- and load
compensations are not included.
[1] * VVC+ Normal running mode, including slip- and load
compensations.
1-03 Torque Characteristics
Option: Function:
With more torque characteristics it is
possible to run low energy consuming, as
well as high torque applications.
[0 ] * Constant
Torque
Motor shaft output provides constant
torque under variable speed control.
[2] Automatic
Energy Optimi-
sation
This function automatically optimizes
energy consumption in centrifugal pump
and fan applications. See 14-41 AEO
Minimum Magnetisation.
1-05 Hand Mode Configuration
Option: Function:
This parameter is only relevant when 1-00
Configuration Mode is set to [3] Process Closed
Loop. The parameter is used for determining
the reference or setpoint handling when
changing from Auto Mode to Hand Mode on
the LCP.
[0] Speed
Open
Loop
In Hand Mode the drive always runs in Open
Loop configuration regardless of setting in 1-00
Configuration Mode. Local potentiometer (if
present) or Arrow up/down determines output
1-05 Hand Mode Configuration
Option: Function:
frequency limited by Motor Speed High/Low
Limit (4-14 Motor Speed High Limit and 4-12
Motor Speed Low Limit).
[2] * As config-
uration in
1-00
Configu-
ration
Mode.
If 1-00 Configuration Mode is set to [1] Open
Loop function is as described above.
If 1-00 Configuration Mode is set to [3] Process
Closed Loop changing from Auto mode to Hand
mode results in a setpoint change via local
potentiometer or Arrow up/down. The change
is limited by Reference Max/Min (3-02 Minimum
Reference and 3-03 Maximum Reference).
4.2.1 1-2* Motor Data
Enter the correct motor nameplate data (power, voltage,
frequency, current and speed).
Run AMT, see 1-29 Automatic Motor Tuning (AMT).
Factory settings for advanced motor data, parameter group
1-3* Adv. Motor Data, are automatically calculated.
NOTE
Parameters in parameter group 1-2* Motor Data cannot be
adjusted while motor runs.
1-20 Motor Power [kW]/[HP] (P
m.n
)
Option: Function:
Enter motor power from nameplate
data.
Two sizes down, one size up from
nominal VLT rating.
[1] 0.09 kW/0.12 HP
[2] 0.12 kW/0.16 HP
[3] 0.18kW/0.25 HP
[4] 0.25 kW/0.33 HP
[5] 0.37kW/0.50 HP
[6] 0.55 kW/0.75 HP
[7] 0.75 kW/1.00 HP
[8] 1.10 kW/1.50 HP
[9] 1.50 kW/2.00 HP
[10] 2.20 kW/3.00 HP
[11] 3.00 kW/4.00 HP
[12] 3.70 kW/5.00 HP
[13] 4.00 kW/5.40 HP
[14] 5.50 kW/7.50 HP
[15] 7.50 kW/10.0 HP
[16] 11.00 kW/15.00 HP
[17] 15.00 kW/20.00 HP
[18] 18.50 kW/25.00 HP
[19] 22.00 kW/29.50 HP
[20] 30.00 kW/40.00 HP
Parameter Descriptions
VLT
®
Micro Drive FC 51 Programming Guide
14 MG02C602 - VLT
®
is a registered Danfoss trademark
44

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 51 Series and is the answer not in the manual?

Danfoss FC 51 Series Specifications

General IconGeneral
BrandDanfoss
ModelFC 51 Series
CategoryDC Drives
LanguageEnglish

Related product manuals