5.2 Derating Limits
To ensure that the inverters can produce the rated power,
measurement inaccuracies are taken into account when
enforcing the derating limits stated in Table 5.5.
(Limit = rated value + tolerance).
FLX series
5 6 7 8 9 10 12.5 15 17
Grid current, per phase 7.5 A 9.0 A 10.6 A 12.1 A 13.6 A 15.1 A 18.8 A 22.6 A 25.6 A
Grid power, total 5150 W 6180 W 7210 W 8240 W 9270 W 10300 W 12875 W 15450 W 17510 W
Table 5.5 Derating Limits
5.3 Conformity
FLX series
International
Standards
5 6 7 8 9 10 12.5 15 17
Directive LVD 2006/95/EC
Directive EMC 2004/108/EC
Safety IEC 62109-1/IEC 62109-2
Integrated PV load switch VDE 0100-712
Functional Safety IEC 62109-2
EMC immunity
EN 61000-6-1
EN 61000-6-2
EMC emission
EN 61000-6-3
EN 61000-6-4
Utility interference EN 61000-3-2/-3 EN 61000-3-11/-12
CE Yes
Utility characteristics
IEC 61727
EN 50160
S0 Energy Meter (option) EN62053-31 Annex D
Table 5.6 International Standards Compliance