Option 33 - Enable On at upper limit
This enables an ON function to be selected if a set point
above the upper limit is selected. Press + until Option
33 is displayed, use V and Λ to select required setting.
Setting 0 Disabled (factory setting)
Setting 1 Enabled
Option 34 - Select On/O or on/o load compensation
This allows the thermostat to be set to run in On/O
mode or for a On/O load Compensation cycle rate to
be selected. Press + until Option 34 is displayed, use V
and Λ to select required setting.
0 On/O
3 3 cycles per hour
6 6 cycles per hour (factory setting)
9 9 cycles per hour
12 12 cycles per hour
Option 35 - Set integration time (Option 34 set to 3, 6, 9 or 12)
(seek advice prior to adjusting)
This adjusts the integration time of the load
compensation algorithm to increase control accuracy.
It should only be adjusted after seeking advice from
the manufacturer. Press + until Option 35 is displayed,
use V and Λ to select required setting.
2.5 Integration time set to 2.5% (factory setting)
5 Integration time set to 5%
10 Integration time set to 10%
Option 36 - Set temperature override rule
This establishes the degree of temperature override
available to the user. Press + until Option 36 is
displayed, use V and Λ to select required setting.
Setting 0 No limit (factory setting)
Setting 1 Limited to ±2°C
Setting 2 No override allowed