VLT® 7000 Booster
■ Quick Menu
The QUICK MENU key gives access to 41 of
the most important setup parameters of the
drive. After programming, the drive will, in many
cases, be ready for operation.
Quick Menu
Number
Parameter
number
Name Units Range Factory Setting
1 102 Motor Power KW/HP 1,1-55/1,5-75 kW
2 103 Motor Voltage Volt 380-460
3 104 Motor Frequency Hz 50/60 Hz 50 Hz
4 105 Motor Current Amps 0-Ivlt,max -
5 106 Rated motor speed RPM 1200 - f m,n x 60 -
6 201 Min. Frequency Hz 0,0 - fmax 20 Hz
7 202 Max. Frequency Hz fmin - 120/1000 50 Hz
8 206 Ramp up time seconds 1-60 See table below
9 207 Ramp down time Seconds 1-60 See table below
10 415 Pressure unit Bar
11 413 Minimum Feedback Par. 415 999.999,999-FBmax 0.000
12 414 Maximum Feedback Par. 415 FBmin - 999.999,999 100.000
13 227 Warning Low Feedback Par. 415 999.999,999-FBhigh -999.999.999
14 228 Warning High Feedback Par. 415 FBlow - 999.999,999 999.999.999
15 204 Minimum reference Par. 415 Min. feedback - Max. reference 0.000
16 205 Maximum reference Par. 415 Min. reference - Max. feedback 50.000
17 700 Cascade mode 1-14 1
18 701 Pump Combination DOM
1
19 702 Staging bandwidth % 0-100 5
20 703 SBW destage delay Sec. 0-3000 10
21 704 SBW stage delay Sec. 0-3000 10
22 705 Override bandwidth % 0-100 (100=Off) Off
23 706 Override timer Sec. 0-300 10
24 707 Destage by timer Sec. 0-301 (301=Off) Off
25 708 Staging frequency % 0-100% of f
max
90
26 709 Destaging frequency % 0-100% of f
max
50
27 710 Delay before running on mains ms 0-2000 500
28 711 Sleep/AUX timer Sec. 0-300 (301 = Off) DOM
2
29 712 Sleep/AUX frequency Hz Par. 201 - Par. 713 20 Hz
30 713 Wakeup/disable AUX -
frequency
Hz Par. 712 - Par. 202 50 Hz
31 714 Boost setpoint % 1-200% of Setpoint 1 100%
32 418 Setpoint 1 (H0) Par. 415 Par. 413-Par. 414 0.000
33 419 Setpoint 2 (H1) Par. 415 Par. 413-Par. 414 0.000
34 719 Pump enable Indexed par. 0-1 1
35 720 Pump running hours Hours 0,0-999.999,9 -
36 721 Setpoints Par. 415 0,0-999.999,9 -
37 420 Normal/inverse control Normal/inverse Normal
38 422 PID start up frequency Hz f
min
-f
max
0
39 427 PID Lowpass filter time Sec. 0.01-10.00 0.2
40 423 PID Proportional Gain Factor 0.00-10.00 0.3
41 424 PID Integrator time Sec. 0.01-9999.00 Off
VLT Type Ramp up time
(par.206)
Ramp down time
(par.207)
7002-7011 1 sec. 1 sec.
7016-7062 3 sec. 2 sec.
7072 5 sec. 3 sec.
1) Depending on Mode, please refer to par. 700.
2) Depending on Mode, with AUX pump: 150
sec., without AUX pump: OFF.