VLT® 7000 Booster
Programming
Function:
This output can act both as a digital or an analogue
output. If used as a digital output (data value [0]-[59]), a
0/24 V DC signal is transmitted; if used as an analogue
output, either a 0-20 mA signal, a 4-20 mA signal or a
pulse sequence of 0-32000 pulses is transmitted.
Description of choice:
No function. Selected if the frequency converter
is not to react to signals.
Drive ready. The frequency converter control
card receives a supply voltage and the frequency
con-verter is ready for operation.
Stand by. The frequency converter is ready
for operation, but no start command has
been given. No warning.
Running. A start command has been given.
Running at ref. value. Speed according to reference.
Running, no warning. A start command has
been given. No warning.
Local reference active. The output is active
when the motor is controlled by means of the
local reference via the control unit.
Remote references active. The output is active
when the frequency converter is controlled by
means of the remote references.
Alarm. The output is activated by an alarm.
Alarm or warning. The output is activated
by an alarm or a warning.
No alarm. The output is active when there is no alarm.
Current limit. The output current is greater than the
value programmed in parameter 215 Current limit I
LIM
.
Safety interlock. The output is active when
terminal 27 is a logic ‘1’ and Safety interlock
has been selected on the input.
Start command active. Isactivewhenthereisastart
command or the output frequency is above 0.1 Hz.
Reversing. Thereis24VDContheoutputwhen
the motor rotates anti-clockwise. When the motor
rotates clockwise, the value is 0 V DC.
Thermal warning. The temperature limit in either
the motor, the frequency converter or a thermistor
connected to an analogue input has been exceeded.
Hand mode active. The output is active when the
frequency converter is in Hand mode.
Auto mode active. Theoutputisactivewhenthe
frequency converter is in Auto mode.
Sleep mode. Active when the frequency
conver-ter is in Sleep mode.
Output frequency lower than f
LOW
. The output
frequency is lower than the value set in parameter
223 Warning: Low frequency, f
LOW
.
Outout frequency higher than f
high
. The output
frequency is higher than the value set in parameter
224 Warning: High frequency, f
HIGH
.
Outoffrequencyrange. The output frequency
is outside the frequency range programmed in
parameter 223 Warning: Low frequency, f
LOW
and
224 Warning: High f requency, f
HIGH
.
Output current lower than I
LOW
. The output
current is lower than the value set in parameter
221 Warning: Low current, I
LOW
.
Output current higher than I
HIGH
.Theoutput
current is higher than the value set in parameter
222 Warning: High current, I
HIGH
.
Out of current range. The output current is outside
the range programmed in parameter 221 Warning: Low
current, I
LOW
and 222 Warning, High current, I
HIGH
.
Out of feedback range. The feedback signal
is out-side the range programmed in parameter
227 Warning: Low feedback, FB
LOW
and 228
Warning: High feedback, FB
HIGH
.
Out of reference range. The reference lies
outside the range programmed in parameter 225
Warning: Low reference, Ref
LOW
and 226Warning,
High reference, Ref
HIGH
.
Relay 123. This function is only used when a
profibus option card is installed.
Mains imbalance. This output is activated at
too high mains imbalance or when a phase is
missing in the mains supply. Check the mains
voltage to the frequency converter.
0-f
MAX
0-20 mA and
0-f
MAX
4-20 mA and
0-f
MAX
0-32000 p which generates an output sig-nal
proportional to the output frequency in the interval 0 -
f
MAX
(parameter 202 Output frequency, high limit, f
MAX
).
✭
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.70.A1.02 - VLT is a registered Danfoss trademark