FC 202, P45KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[μsec]
Vpeak
[kV]
dU/dt
[kV/μsec]
5 480 0.368 1.270 2.853
50 480 0.536 1.260 1.978
100 480 0.680 1.240 1.426
150 480 0.712 1.200 1.334
FC 202, P55KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[μsec]
Vpeak
[kV]
dU/dt
[kV/μsec]
15 480 0.256 1.230 3.847
50 480 0.328 1.200 2.957
100 480 0.456 1.200 2.127
150 480 0.960 1.150 1.052
FC 202, P75KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[μsec]
Vpeak
[kV]
dU/dt
[kV/μsec]
5 480 0.371 1.170 2.523
FC 202, P90KT4
Cable
length [m]
Mains
voltage [V]
Rise time
[μsec]
Vpeak
[kV]
dU/dt
[kV/μsec]
5 480 0.371 1.170 2.523
High Power Range:
FC 202, P110 - P250, T4
Cable
length [m]
Mains
voltage [V]
Rise time
[μsec]
Vpeak
[kV]
dU/dt
[kV/μsec]
30 400 0.34 1.040 2.447
FC 202, P315 - P1M0, T4
Cable
length [m]
Mains
voltage [V]
Rise time
[μsec]
Vpeak
[kV]
dU/dt
[kV/μsec]
30 500 0.71 1.165 1.389
30 400 0.61 0.942 1.233
FC 202, P110 - P400, T7
Cable
length [m]
Mains
voltage [V]
Rise time
[μsec]
Vpeak
[kV]
dU/dt
[kV/μsec]
30 690 0.38 1.513 3.304
30 575 0.23 1.313 2.750
30
690
1)
1.72 1.329 0.640
1) With Danfoss dU/dt filter.
3 VLT AQUA Selection VLT
®
AQUA Drive Design Guide
58
MG.20.N5.02 - VLT
®
is a registered Danfoss trademark
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive Series and is the answer not in the manual?

Danfoss VLT AQUA Drive Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive Series
CategoryMedia Converter
LanguageEnglish

Related product manuals