Par. No. # Parameter description Default value 4-set-up Change during opera-
tion
Conver-
sion index
Type
29-0* Pipe Fill
29-00 Pipe Fill Enable [0] Disabled 2 set-ups FALSE - Uint8
29-01 Pipe Fill Speed [RPM] SR All set-ups TRUE 67 Uint16
29-02 Pipe Fill Speed [Hz] SR All set-ups TRUE -1 Uint16
29-03 Pipe Fill Time 0.00 s All set-ups TRUE -2 Uint32
29-04 Pipe Fill Rate 0.001 ProcessCtrlUnit All set-ups TRUE -3 Int32
29-05 Filled Setpoint 0.000 ProcessCtrlUnit All set-ups TRUE -3 Int32
8.3.24. Water Application Functions 29-**
VLT
®
AQUA Drive
Operating Instructions
8. How to programme the frequency converter
MG.20.M4.02 - VLT
®