Mains Supply 1 x 200 - 240 VAC - Normal overload 110% for 1 minute
Frequency converter
Typical Shaft Output [kW]
P5K
5
P7K
5
P15K P22K
Typical Shaft Output [HP] at 240 V 7.5 10 20 30
IP 21 / NEMA 1 B1 B2 C1 C2
IP 55 / NEMA 12 B1 B2 C1 C2
IP 66 / NEMA 12 B1 B2 C1 C2
Output current
Continuous
(1 x 200-240 V) [A]
24.2 30.8 59.4 88
Intermittent
(1 x 200-240 V) [A]
26.6
33.4 65.3 96.8
Continuous kVA
(208 V AC) [kVA]
5.00 6.40 12.27 18.30
Max. cable size:
(mains, motor, brake)
[[mm
2
/ AWG]
2)
10/7 35/2 50/1/0 95/4/0
Max. input current
Continuous
(1 x 200-240 V ) [A]
46 59 111 172
Intermittent
(1 x 200-240 V ) [A]
50.6
64.9 122.1 189.2
Max. pre-fuses
1)
[A]
80 100 150 200
Environment
Estimated power loss
at rated max. load [W]
4)
110 150 300 440
Weight enclosure IP 21 [kg] 23 27 45 65
Weight enclosure IP 55 [kg] 23 27 45 65
Weight enclosure IP 66 [kg] 23
27 45 65
Efficiency
3)
0.98 0.98 0.98 0.98