5.1.5. Mains connection for A2 and A3
Illustration 5.2: First mount the two screws on the mounting plate, slide it into place and tighten fully.
Illustration 5.3: When mounting cables, first mount and tighten earth cable.
The earth connection cable cross section must be at least 10 mm
2
or 2 rated mains wires terminated separately according to
EN 50178/
IEC 61800-5-1
.