EasyManua.ls Logo

Danfoss VLT AQUA Drive - Page 58

Danfoss VLT AQUA Drive
159 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.1.11. Initialisation to Default Settings
There are two ways to initialise the frequency converter to default: Recommended initialisation and manual initialisation.
Please be aware that they have different impact according to the below description.
Recommended initialisation (via par. 14-22)
1. Select par. 14-22
2. Press [OK]
3. Select “Initialisation” ( for NLCP select “2” )
4. Press [OK]
5. Remove power to unit and wait for display to turn off.
6. Reconnect power and the frequency converter is reset. Note
that first start-up takes a few more seconds.
7. Press [Reset]
Par. 14-22 initialises all except:
Par. 14-50
RFI 1
Par. 8-30
Protocol
Par. 8-31
Address
Par. 8-32
Baud Rate
Par. 8-35
Minimum Response Delay
Par. 8-36
Max Response Delay
Par. 8-37
Max Inter-char Delay
Par. 15-00 to par.
15-05
Operating data
Par. 15-20 to par.
15-22
Historic log
Par. 15-30 to par.
15-32
Fault log
NB!
Parameters selected in
Personal Menu
, will stay present, with default factory setting.
Manual initialisation
NB!
When carrying out manual initialisation, serial communication, RFI filter settings (par. 14-50) and fault log settings are reset.
Removes parameters selected in
Personal Menu
.
1. Disconnect from mains and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while
power up for Graphical LCP (GLCP).
2b. Press [Menu] while power up for LCP 101, Numerical Display
3. Release the keys after 5 s.
4. The frequency converter is now programmed according to
default settings.
This parameter initialises all except:
15-00
Operating Hours
15-03
Power-up's
15-04
Over temp's
15-05
Over volt's
7.1.12. RS-485 Bus Connection
One or more frequency converters can be connected to a controller (or
master) using the RS-485 standard interface. Terminal 68 is connected
to the P signal (TX+, RX+), while terminal 69 is connected to the N signal
(TX-,RX-).
If more than one frequency converter is connected to a master, use par-
allel connections.
Illustration 7.9: Connection example.
7. How to operate the frequency converter
VLT
®
AQUA Drive
Operating Instructions
58
MG.20.M4.02 - VLT
®
is a registered Danfoss trademark
7

Table of Contents

Related product manuals