Setting in Par. 5-1* Setting in Par. 25-06
[0] No [1] Yes
[130] Pump1 Interlock Controlled by RELAY1
(only if not lead pump)
Frequency Converter controlled
(cannot be interlocked)
[131] Pump2 Interlock Controlled by RELAY2 Controlled by RELAY1
[132] Pump3 Interlock Controlled by RELAY3 Controlled by RELAY2
[133] Pump4 Interlock Controlled by RELAY4 Controlled by RELAY3
[134] Pump5 Interlock Controlled by RELAY5 Controlled by RELAY4
[135] Pump6 Interlock Controlled by RELAY6 Controlled by RELAY5
[136] Pump7 Interlock Controlled by RELAY7 Controlled by RELAY6
[137] Pump8 Interlock Controlled by RELAY8 Controlled by RELAY7
[138] Pump9 Interlock Controlled by RELAY9 Controlled by RELAY8
5-13 Terminal 29 Digital Input
Option: Function:
[0]
*
No Operation Same options and functions as par. 5-1*
Digital Inputs
.
5-14 Terminal 32 Digital Input
Option: Function:
[0]
*
No Operation Same options and functions as par. 5-1*
Digital Inputs
, except for
Pulse input
.
5-15 Terminal 33 Digital Input
Option: Function:
[0]
*
No Operation Same options and functions as par. 5-1*
Digital Inputs
.
5-40 Function Relay
Array [8] (Relay 1 [0], Relay 2 [1], Relay 7 [6], Relay 8 [7], Relay 9 [8])
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array parameter.
[0] No Operation
[1] Control Ready
[2] Drive Ready
[3] Drive Ready/Remote
[4] Stand-by/No Warning
[5]
*
Running
[6] Running/No Warning
[8] Run on Ref./No Warn-
ing
[9] Alarm
[10] Alarm or Warning
[11] At Torque Limit
[12] Out of Current Range
[13] Below Current, low
[14] Above Current, high
[15] Out of Speed Range
VLT
®
AQUA Drive
Operating Instructions
8. How to programme the frequency converter
MG.20.M4.02 - VLT
®
is a registered Danfoss trademark
79