8-05 End-of-Timeout Function
Option: Function:
[1] * Resume set-
up
Resumes the set-up active before the time-
out.
8-06 Reset Control Word Timeout
This parameter is active only when [0] Hold set-up has been
selected in 8-05 End-of-Timeout Function.
Option: Function:
[0] * Do not reset
Retains the set-up specified in 8-04 Control
Word Timeout Function, following a control
word time-out.
[1] Do reset Returns the frequency converter to the
original set-up following a control word time-
out. The frequency converter performs the
reset and then immediately reverts to the [0]
Do not reset setting
8-08 Readout Filtering
If the speed feedback value readouts on fieldbus are fluctuating,
this function is used. Select filtered if the function is required. A
power-cycle is required for changes to take effect.
Option: Function:
[0] * Motor Data Std-
Filt.
Select [0] for normal bus
readouts.
[1] Motor Data LP-
Filter
Select [1] for filtered bus
readouts of the following
parameters:
16-10 Power [kW]
16-11 Power [hp]
16-12 Motor Voltage
16-14 Motor Current
16-16 Torque [Nm]
16-17 Speed [RPM]
16-22 Torque [%]
16-25 Torque [Nm] High
3.10.2 8-1* Ctrl. Word Settings
8-10 Control Word Profile
Select the interpretation of the control and status words
corresponding to the installed fieldbus. Only the selections valid
for the fieldbus installed in slot A will be visible in the LCP
display.
For guidelines in selection of [0] FC profile and [1] PROFIdrive
profile please refer to the Serial communication via RS-485
Interface section in the Design Guide.
For additional guidelines in the selection of [1] PROFIdrive profile,
please refer to the Operating Instructions for the installed
fieldbus.
Option: Function:
[0] * FC profile
[1] PROFIdrive profile
8-10 Control Word Profile
Select the interpretation of the control and status words
corresponding to the installed fieldbus. Only the selections valid
for the fieldbus installed in slot A will be visible in the LCP
display.
For guidelines in selection of [0] FC profile and [1] PROFIdrive
profile please refer to the Serial communication via RS-485
Interface section in the Design Guide.
For additional guidelines in the selection of [1] PROFIdrive profile,
please refer to the Operating Instructions for the installed
fieldbus.
Option: Function:
[5] ODVA
[7] CANopen DSP 402
[8] MCO
8-13 Configurable Status Word STW
Option: Function:
[0] No function The input is always low.
[1] * Profile Default Depended on the profile set in
8-10 Control Profile.
[2] Alarm 68 Only The input goes high whenever
Alarm 68 is active and goes low
whenever no alarm 68 is actived
[3] Trip excl Alarm 68
[10] T18 DI status
[11] T19 DI status
[12] T27 DI status
[13] T29 DI status
[14] T32 DI status
[15] T33 DI status
[16] T37 DI status The input goes high whenever T37
has 0 V and goes low whenever
T37 has 24 V
[21] Thermal warning
[30] Brake fault (IGBT)
[40] Out of ref range
[41] Load throttle active
[60] Comparator 0
[61] Comparator 1
[62] Comparator 2
[63] Comparator 3
[64] Comparator 4
[65] Comparator 5
[70] Logic Rule 0
[71] Logic Rule 1
[72] Logic Rule 2
[73] Logic Rule 3
[74] Logic Rule 4
[75] Logic Rule 5
[80] SL digital out A
[81] SL digital out B
[82] SL digital out C
[83] SL digital out D
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
106 MG33ME02 - VLT
®