3.21 Parameters: 35-** Sensor Input Option
3.21.1 35-0* Temp. Input Mode (MCB 114)
35-00 Term. X48/4 Temp. Unit
Select the unit to be used with temperature input X48/4 settings
and readouts:
Option: Function:
[60] * °C
[160] °F
35-01 Term. X48/4 Input Type
View the temperature sensor type detected at input X48/4:
Option: Function:
[0] * Not Connected
[1] PT100 2-wire
[3] PT1000 2-wire
[5] PT100 3-wire
[7] PT1000 3-wire
35-02 Term. X48/7 Temp. Unit
Select the unit to be used with temperature input X48/7 settings
and readouts:
Option: Function:
[60] * °C
[160] °F
35-03 Term. X48/7 Input Type
View the temperature sensor type detected at input X48/7:
Option: Function:
[0] * Not Connected
[1] PT100 2-wire
[3] PT1000 2-wire
[5] PT100 3-wire
[7] PT1000 3-wire
35-04 Term. X48/10 Temp. Unit
Select the unit to be used with temperature input X48/10
settings and readouts:
Option: Function:
[60] * °C
[160] °F
35-05 Term. X48/10 Input Type
View the temperature sensor type detected at input X48/10:
Option: Function:
[0] * Not Connected
[1] PT100 2-wire
[3] PT1000 2-wire
[5] PT100 3-wire
[7] PT1000 3-wire
35-06 Temperature Sensor Alarm Function
Select the alarm function:
Option: Function:
[0] Off
[2] Stop
[5] * Stop and trip
3.21.2 35-1* Temp. Input X48/4 (MCB 114)
35-14 Term. X48/4 Filter Time Constant
Range: Function:
0.001 s* [0.001 -
10.000 s]
Enter the filter time constant. This is a
first-order digital low pass filter time
constant for suppressing electrical noise
in terminal X48/4. A high time constant
value improves dampening but also
increases the time delay through the
filter.
35-15 Term. X48/4 Temp. Monitor
This parameter gives the possibility of enabling or disabling the
temperature monitor for terminal X48/4. The temperature limits
can be set in 35-16 Term. X48/4 Low Temp. Limit and 35-17 Term.
X48/4 High Temp. Limit.
Option: Function:
[0] * Disabled
[1] Enabled
35-16 Term. X48/4 Low Temp. Limit
Range: Function:
Size related* [ -50. - par.
35-17 ]
Enter the minimum temperature
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/4.
35-17 Term. X48/4 High Temp. Limit
Range: Function:
Size related* [ par. 35-16 -
204. ]
Enter the maximum temperature
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/4.
Parameter Descriptions