4.1.1 Conversion
The various attributes of each parameter are displayed in
Factory Setting. Parameter values are transferred as whole
numbers only. Conversion factors are therefore used to
transfer decimals.
4-12 Motor Speed Low Limit [Hz] has a conversion factor of
0.1. To preset the minimum frequency to 10 Hz, transfer
the value 100. A conversion factor of 0.1 means that the
value transferred is multiplied by 0.1. The value 100 is
therefore read as 10.0.
Examples:
0s conversion index 0
0.00s conversion index -2
0ms conversion index -3
0.00ms conversion index -5
Conversion index Conversion factor
100
75
74
67
6 1000000
5 100000
4 10000
3 1000
2 100
1 10
0 1
-1 0.1
-2 0.01
-3 0.001
-4 0.0001
-5 0.00001
-6 0.000001
-7 0.0000001
Table 4.2 Conversion Table
4.1.2
Active/Inactive Parameters in Different Drive Control Modes
+ = active
- = not active
1-10 Motor Construction AC motor PM Non salient Motor
1-01 Motor Control Principle
U/f mode
VVC
plus
Flux sensorless
Flux w/ motor
feedback
U/f mode
Flux
sensorless
Flux w/
motor
feedback
1-00 Configuration Mode
[0] Speed Open Loop + + + -
[1] Speed Closed Loop - + - +
[2] Torque - - - +
[3] Process + + + -
[4] Torque Open Loop - + - -
[5] Wobble + + + +
[6] Surface Winder + + + -
[7] Ext. PID Open Loop + + + -
[8] Ext. PID Closed Loop - + - +
1-02 Flux Motor Feedback Source - - - +
1-03 Torque Characteristics
-
+
see 1, 2, 3)
+
see 1, 3, 4)
+
see 1, 3, 4)
1-04 Overload Mode + + + + + + +
1-05 Local Mode Configuration + + + + + + +
1-06 Clockwise Direction + + + + + + +
1-20 Motor Power [kW]
(Par. 023 = International)
+ + + +
1-21 Motor Power [HP]
(Par. 023 = US)
+ + + +
1-22 Motor Voltage + + + +
1-23 Motor Frequency + + + +
1-24 Motor Current + + + +
Parameter Lists
VLT
®
AutomationDrive Programmming Guide
160 MG33ME02 - VLT
®
is a registered Danfoss trademark
44

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 300 Series

Related product manuals