8-57 Profidrive OFF2 Select
Select control of the OFF2 selection via the terminals (digital
input) and/or via the fieldbus. This parameter is active only when
par. 8-01 Control Site is set to [0] Digital and ctrl. word and par.
8-10 is set to [1] Profidrive profile.
Option: Function:
[0] Digital input
[1] Bus
[2] Logic AND
[3] * Logic OR
8-58 Profidrive OFF3 Select
Select control of the OFF3 selection via the terminals (digital
input) and/or via the fieldbus. This parameter is active only when
par. 8-01 Control Site is set to [0] Digital and control word and
par. 8-10 is set to [1] Profidrive profile.
Option: Function:
[0] Digital input
[1] Bus
[2] Logic AND
[3] * Logic OR
3.10.6 8-8* FC Port Diagnostics
These parameters are used for monitoring the Bus
communication via the FC Port.
8-80 Bus Message Count
Range: Function:
0 * [0 - 0 ] This parameter shows the number of valid
telegrams detected on the bus.
8-81 Bus Error Count
Range: Function:
0 * [0 - 0 ] This parameter shows the number of telegrams
with faults (e.g. CRC fault), detected on the bus.
8-82 Slave Messages Rcvd
Range: Function:
0 * [0 - 0 ] This parameter shows the number of valid
telegrams addressed to the slave, sent by the
frequency converter.
8-83 Slave Error Count
Range: Function:
0 * [0 - 0 ] This parameter shows the number of error
telegrams, which could not be executed by the
frequency converter.
3.10.7 8-9* Bus Jog
8-90 Bus Jog 1 Speed
Range: Function:
100 RPM* [0 - par. 4-13
RPM]
Enter the jog speed. Activate this
fixed jog speed via the serial port
or fieldbus option.
8-91 Bus Jog 2 Speed
Range: Function:
200 RPM* [0 - par. 4-13
RPM]
Enter the jog speed. Activate this
fixed jog speed via the serial port
or fieldbus option.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark 111
3