13-51 SL Controller Event
Array [20]
Option: Function:
[93] ATEX ETR freq. alarm
Selectable if 1-90 Motor Thermal
Protection is set to [20] or [21]. If
the warning 165 ATEX ETR
freq.lim.warning is active, the
output will be 1.
[94] RS Flipflop 0
[95] RS Flipflop 1
[96] RS Flipflop 2
[97] RS Flipflop 3
[98] RS Flipflop 4
[99] RS Flipflop 5
[100] RS Flipflop 6
[101] RS Flipflop 7
13-52 SL Controller Action
Array [20]
Option: Function:
[0] * DISABLED Select the action corresponding to the SLC
event. Actions are executed when the
corresponding event (defined in 13-51 SL
Controller Event) is evaluated as true. The
following actions are available for selection:
[0] *DISABLED
[1] No action
[1] No action
[2] Select set-up 1
[2] Select set-up 1 - changes the active set-
up (0-10 Active Set-up) to ‘1’.
If the set-up is changed, it will merge with
other set-up commands coming from
either the digital inputs or via a fieldbus.
[3] Select set-up 2
[3] Select set-up 2 - changes the active set-
up 0-10 Active Set-up) to ‘2’.
If the set-up is changed, it will merge with
other set-up commands coming from
either the digital inputs or via a fieldbus.
[4] Select set-up 3
[4] Select set-up 3 - changes the active set-
up (0-10 Active Set-up) to ‘3’.
If the set-up is changed, it will merge with
other set-up commands coming from
either the digital inputs or via a fieldbus.
[5] Select set-up 4
[5] Select set-up 4 - changes the active set-
up (0-10 Active Set-up) to ‘4’.
If the set-up is changed, it will merge with
other set-up commands coming from
either the digital inputs or via a fieldbus.
[10] Select preset
ref 0
[10] Select preset reference 0 – selects preset
reference 0.
If the active preset reference is changed, it
will merge with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
13-52 SL Controller Action
Array [20]
Option: Function:
[11] Select preset
ref 1
[11] Select preset reference 1 – selects preset
reference 1.
If the active preset reference is changed, it
will merge with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[12] Select preset
ref 2
[12] Select preset reference 2 – selects preset
reference 2.
If the active preset reference is changed, it
will merge with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[13] Select preset
ref 3
[13] Select preset reference 3 – selects preset
reference 3.
If the active preset reference is changed, it
will merge with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[14] Select preset
ref 4
[14] Select preset reference 4 – selects preset
reference 4.
If the active preset reference is changed, it
will merge with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[15] Select preset
ref 5
[15] Select preset reference 5 – selects preset
reference 5.
If the active preset reference is changed, it
will merge with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[16] Select preset
ref 6
[16] Select preset reference 6 – selects preset
reference 6.
If the active preset reference is changed, it
will merge with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[17] Select preset
ref 7
[17] Select preset reference 7 - selects preset
reference 7.
If the active preset reference is changed, it
will merge with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[18] Select ramp 1
[18] Select ramp 1 - selects ramp 1.
[19] Select ramp 2
[19] Select ramp 2 - selects ramp 2.
[20] Select ramp 3
[20] Select ramp 3 - selects ramp 3.
[21] Select ramp 4
[21] Select ramp 4 - selects ramp 4.
[22] Run
[22] Run - issues a start command to the
frequency converter.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark 127