14-90 Fault Level
Option: Function:
[2] Trip
14-90 Fault Level
Option: Function:
[3] Trip Lock
Failure Alarm Off Warning Trip Trip Lock
10 V low 1 X D
24 V low 47 X D
1.8 V supply low 48 X D
Voltage limit 64 X D
Earth fault during ramping 14 D X
Earth fault 2 during cont. operation 45 D X
Torque Limit 12 X D
Over Current 13 X D
Short Circuit 16 X D
Heatsink temperature 29 X D
Heatsink sensor 39 X D
Control card temperature 65 X D
Power card temperature 6
2)
X D
Heatsink temperature
1)
244 X D
Heatsink sensor
1)
245 X D
Power card temperature
1)
247
Table 3.28 Table for Selection of Choice of Action when Selected Alarm Appears
D = Default setting. x = possible selection.
1) Only high power drives
In FC small and medium A69 is only a warning
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark 137
3