35-45 Term. X48/2 High Ref./Feedb. Value
Range: Function:
100.000 * [-999999.999 -
999999.999 ]
Enter the reference or feedback
value (in RPM, Hz, bar, etc.) that
corresponds to the voltage or
current set in 35-43 Term. X48/2
High Current.
35-46 Term. X48/2 Filter Time Constant
Range: Function:
0.001 s* [0.001 -
10.000 s]
Enter the filter time constant. This is a
first-order digital low pass filter time
constant for suppressing electrical noise
in terminal X48/2. A high time constant
value improves dampening but also
increases the time delay through the
filter.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
158 MG33ME02 - VLT
®