3-92 Power Restore
Option: Function:
[0] * Off Resets the Digital Potentiometer reference to 0% after
power up.
[1] On Restores the most recent Digital Potentiometer
reference at power up.
3-93 Maximum Limit
Range: Function:
100 %* [-200 - 200
%]
Set the maximum permissible value for
the resultant reference. This is advisable if
the Digital Potentiometer is used for fine
tuning of the resulting reference.
3-94 Minimum Limit
Range: Function:
-100 %* [-200 - 200
%]
Set the minimum permissible value for
the resultant reference. This is advisable
if the Digital Potentiometer is used for
fine tuning of the resulting reference.
3-95 Ramp Delay
Range: Function:
Size
related*
[ 0 -
0 ]
Enter the delay required from activation of
the digital potentiometer function until the
frequency converter starts to ramp the
reference. With a delay of 0 ms, the
reference starts to ramp as soon as
INCREASE/ DECREASE is activated. See also
3-91 Ramp Time.