11.3 General Technical Data - Adjustable Frequency Drive
Line power supply (L1, L2, L3)
Supply voltage 380–480 V +5%
AC line voltage low/line drop-out:
During low AC line voltage or line drop-out, the adjustable frequency drive continues until the intermediate circuit voltage drops
below the minimum stop level, corresponding to 15% below the lowest rated supply voltage. Power-up and full torque cannot be
expected at AC line voltage lower than 10% below the lowest rated supply voltage.
Supply frequency 50/60 Hz ±5%
Max. temporary imbalance between line phases 3.0% of rated supply voltage
True power factor (λ) > 0.98 nominal at rated load
Displacement power factor (cosφ) near unity (> 0.98)
THiD < 5%
Switching on input supply L1, L2, L3 (power-ups) maximum once/2 min.
Environment according to EN60664-1 Overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 480/690 V
maximum.
Motor output (U, V, W)
Output voltage 0–100% of supply voltage
Output frequency 0–590* Hz
Switching on output Unlimited
Ramp times 0.01–3600 s
* Voltage and power dependent
Torque characteristics
Starting torque (constant torque) maximum 160% for 1 m.
*
Starting torque maximum 180% up to 0.5 s
*
Overload torque (constant torque) maximum 160% for 1 m.
*
*Percentage relates to nominal torque of the unit.
Cable lengths and cross-sections
Max. motor cable length, shielded/armored 500 ft [150 m]
Max. motor cable length, non-shielded/unarmored 1,000 ft [300 m]
Max. cross-section to motor, line power, load sharing, and brake *
Maximum cross-section to control terminals, rigid wire 1.5 mm
2
/16 AWG (2 x 0.75 mm
2
)
Maximum cross-section to control terminals, flexible cable 1 mm
2
/18 AWG
Maximum cross-section to control terminals, cable with enclosed core 0.5 mm
2
/20 AWG
Minimum cross-section to control terminals 0.25 mm
2
/4 AWG
* See chapter 11.1.1 Line Power Supply 3x380–480 V AC for more information
Specifications
Instruction Manual
156 Danfoss A/S © Rev. 2014-02-07 All rights reserved. MG37A222
1111

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals