FC 300 Design Guide
How to Program
Idle Time [9913]
Paramdb Requests in Queue [9914]
Function:
None [0] No disp lay value chosen
Control Word [1600] Displays the
present control w ord
Reference [Unit] [1601] displays the status valu
e
of terminals 53 or 54 using the unit stated on the
basis of configuration in P.1-00 (RPM or Nm).
Reference % [1602] displays the total
reference (sum of digital/analog/preset/b us/freeze
ref./catch up and slow-d own).
Status Word [binary] [1603] Displays
the present status word
Alarm Word [1604] indicates one or several
alarms in a Hex code.
Warning Word [1605] indicates one or
more warnings in a Hex code.
Extended Status Word [1606] [He
x] indicates
one or more status states in a Hex code.
Power [kW] [1610] sta tes the actual power
consumed by the m otor in kW
.
Power [hp] [1611] states the actual power
consumed by the motor in HP.
Motor voltage [V] [1612] st
ates the voltage
supplied to the motor.
Frequency [Hz] [1613] gives the motor
frequency, i.e. the ou
tput frequency from the
adjustable frequency drive.
Motor Current [A] [1614] states the pha se
current of the motor m
easured as effective value.
Torque [%] [1616] gives the current motor load
in rel ation to the rated motor torque.
Speed [RPM] [1617] D
isplays the speed in
RPM (revolutions per Minute) i.e. the m otor
shaft speed in closed-loop.
Motor Thermal [161
8] states the calculated/es-
timated thermal load on the motor.
DC Link Voltage [V] [ 16 3 0] states the
intermediate ci
rcuit voltage in the adjustable
frequency drive.
Brake Energy /s [1632] states the present brake
power transfer
red to an external brake resistor.
Stated as an instantaneous value.
Brake Energy /2 min [1633] states the brake
power transf
erred to an external brake resistor.
The mean powe r is calculated continuously
for the latest 120 seconds.
Heatsink Temp. [°C] [1634] states the present
heatsink temperature of the adjustable frequency
drive. The cut-out limit is 203 ± 9°F (95 ± 5°C);
resetoccursat158±9°F(70±5°C).
Inverter Thermal [1635] returns the
percentage load of the inverters.
Inv. Nom. Current [1636] The nominal current
of the adjustable frequency drive.
Inv. Max. Current [1637] The maximum current
of the adjustable frequency drive.
SL Controller State [1638] returns the state
of the event executed by the control.
Control Card Temp. [1639] re turns the
temperature on control card.
External Reference [1650] [%] gives the
sum of the external reference as a percentage
(the sum of analog/pulse /bus).
Pulse Reference [1651] [Hz] states the
frequency in H z connected to the programmed
digital inputs (18, 19 or 32, 33).
Feedback [Unit] [1652] returns the re ference
value from programmed digital input(s).
Digital Input [1660] states the signal states
from the 6 digital ter minals (18, 19, 27, 29, 32
and 33) Input 18 corresponds to the bit at the far
left. "0" = signal low; " 1" = signal high.
Terminal 53 Switch Setting [1661]
returns the setting of input terminal 5 3.
Current=0;Voltage=1.
Analog Input 53 [1662] returns the actual value
on input 53 either as reference or protection value.
Terminal 54 Switch Setting [1663]
returns the setting of input terminal 5 4.
Current=0;Voltage=1.
Analog Input 54 [1664] returns the actual value
on input 54 either as reference or protection value.
Analog Output 42 [mA] [1665] re turns the
actual value in mA on o utp u t 42. Selection of
shown value is set in par. 6-50.
Digital Output [bin] [1666] returns the bin
value of all digital outputs.
Freq. Input #29 [Hz] [1667] returns
the actual value of the frequency applied on
terminal 29 as an impulse input.
Freq. Input #33 [Hz] [1668] returns
the actual value of the frequency applied on
terminal 33 as an impulse input.
Pulse output #27 [Hz] [1669] returns the
actual value of impulses applied to ter
minal
27 in digital output mode.
*
default setting ()display text []value for use in communication via serial communication port
135
MG.33.B
3.22 - VLT is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT AutomationDrive FC 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AutomationDrive FC 302 and is the answer not in the manual?

Danfoss VLT AutomationDrive FC 302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AutomationDrive FC 302
CategoryDC Drives
LanguageEnglish

Related product manuals