5-13 Terminal 29 Digital Input
Option: Function:
[14] * Jog
[60] Counter A (up)
[61] Counter A (down)
[63] Counter B (up)
[64] Counter B (down)
5-14 Terminal 32 Digital Input
Option: Function:
Select the function from the available digital
input range.
[0] * No operation
Functions are described under 5-1* Digital
Inputs
5-15 Terminal 33 Digital Input
Option: Function:
Select the function from the available digital
input range and the additional options [60],
[61], [63] and [64]. Counters are used in
Smart Logic Control functions.
[0] * No operation
Functions are described under 5-1* Digital
Inputs
6.6.4 5-3* Digital Outputs
Parameters for configuring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in 5-01 Terminal 27 Mode, and set the I/O
function for terminal 29 in 5-02 Terminal 29 Mode. Digital
outputs appear if 5-01 Terminal 27 Mode or 5-02 Terminal
29 Mode are set to output.
NOTE
These parameters cannot be adjusted while the motor is
running.
NOTE
Only for activating 24 V DC devices − restricted use for
relays.
The digital outputs can be programmed
with these functions:
[0] No operation
Default for all digital outputs and relay
outputs
[1] Control ready The control board receives supply
voltage.
[2] Drive ready The frequency converter is ready for
operation and applies a supply signal on
the control board.
[3] Drive ready /
remote control
The frequency converter is ready for
operation and is in Auto On mode.
[4] Stand-by / no
warning
The frequency converter is ready for
operation. No start or stop command is
been given (start/disable). There are no
warnings.
[5] Running The motor is running.
[6] Running / no
warning
The output speed is higher than the
speed set in 1-81 Min Speed for Function
at Stop [RPM]. The motor is running and
there are no warnings.
[7] Run on
reference / no
warning
The motor runs at reference speed.
[8] Run in range /
no warning
The motor runs in speed range.
[9] Alarm An alarm activates the output. There are
no warnings.
[10] Alarm or
warning
An alarm or a warning activates the
output.
[11] At torque limit
The torque limit set in 4-16 Torque Limit
Motor Mode or 1-17 Voltage filter time
const. has been exceeded.
[12] Out of current
range
The motor current is outside the range
set in 4-18 Current Limit.
[13] Below current,
low
The motor current is lower than set in
4-50 Warning Current Low.
[14] Above current,
high
The motor current is higher than set in
4-51 Warning Current High.
[15] Out of speed
range
The output speed is outside the range set
in 4-52 Warning Speed Low and
4-53 Warning Speed High.
[16] Below speed,
low
The output speed is lower than the
setting in 4-52 Warning Speed Low.
[17] Above speed,
high
The output speed is higher than the
setting in 4-53 Warning Speed High.
[18] Out of
feedback range
The feedback is outside the range set in
4-56 Warning Feedback Low and
4-57 Warning Feedback High.
[19] Below
feedback low
The feedback is below the limit set in
4-56 Warning Feedback Low Warning
Feedback Low.
[20] Above
feedback high
The feedback is above the limit set in
4-57 Warning Feedback High Warning
Feedback High.
[21] Thermal
warning
The thermal warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the brake
resistor, or the thermistor.
[25] Reverse
Reversing. Logic ‘1’ = relay activated, 24 V
DC when CW rotation of the motor. Logic
‘0’ = relay not activated, no signal, when
CCW rotation of the motor.
[26] Bus OK Active communication (no time-out) via
the serial communication port.
[27] Torque limit
and stop
Use in performing a coasting stop and in
torque limit condition. If the frequency
converter has received a stop signal and
is at the torque limit, the signal is Logic
‘0’.
Parameter Descriptions
Operating Instructions VLT
®
CDS302 and CDS303
MG34M302 - VLT
®