CTW/STW
REF/MAV
PCD 2
Read/
Write
PCD 3
Read/
Write
Standard telegram
1
PCD 4
Read/
Write
PCD 5
Read/
Write
PPO 4
PPO 6
PPO 7
PPO 8
Danfoss telegram
(The old PPO type 3)
PCV
CTW/STW REF/MAV
PCD 2
Read/
Write
PCD 3
Read/
Write
PCD 4
Read/
Write
PCD 5
Read/
Write
CTW/STW
REF/MAV
PCD 2
Read/
Write
PCD 3
Read/
Write
PCD 4
Read/
Write
PCD 5
Read/
Write
PCD 6
Read/
Write
PCD 7
Read/
Write
PCD 8
Read/
Write
PCD 9
Read/
Write
CTW/STW REF/MAV
PCD 2
Read/
Write
PCD 3
Read/
Write
PCD 4
Read/
Write
PCD 5
Read/
Write
PCD 6
Read/
Write
PCD 7
Read/
Write
CTW/STW REF/MAV
CTW/STW REF/MAV
PPO 3
CTW/STW REF/MAV
PCD 2
Read/
Write
PCD 3
Read/
Write
PPO 2
PCV
CTW/STW
REF/MAV
PPO 1
PCV
130BD911.10
Illustration 4.1 Available PPO Types
4.2
Process Data
Use the process data part of the PPO to control and
monitor the frequency converter via the PROFIBUS.
4.2.1 Process Control Data
Process control data (PCD) is the process data sent from
the PLC to the frequency converter.
Master/follower
1 2 3 ....... 10
CTW MRV PCD ....... PCD
PCD write
Table 4.1 Process Control Data
PCD 1 contains a 16-bit control word, and each bit controls
a specific function of the frequency converter, see
chapter 4.3 Control Profile.
PCD 2 contains a 16-bit speed setpoint in percentage
format. See chapter 4.2.3 Reference Handling.
The content of PCD 3 to PCD 10 is determined by the
settings in parameter 9-15 PCD Write Configuration and
parameter 9-16 PCD Read Configuration.
4.2.2 Process Status Data
Process status data is the process data sent from the
frequency converter, and contains information about the
current state.
Follower master
1 2 3 ...... 10
STW MAV PCD ...... PCD
PCD read
Table 4.2 Process Status Data
PCD 1 contains a 16-bit status word, and each bit contains
information regarding a possible state of the frequency
converter.
PCD 2 contains per default the value of the current speed
of the frequency converter in percentage format (see
chapter 4.2.3 Reference Handling). PCD 2 can be configured
to contain other process signals.
Control Programming Guide
14 Danfoss A/S © Rev. 05/2014 All rights reserved. MG37G102
44

Table of Contents

Other manuals for Danfoss vlt fcd 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt fcd 302 and is the answer not in the manual?

Danfoss vlt fcd 302 Specifications

General IconGeneral
BrandDanfoss
Modelvlt fcd 302
CategoryController
LanguageEnglish

Related product manuals