9-65 Profile Number
Range: Function:
0* [0 - 0 ] This parameter contains the profile identification.
Byte 1 contains the profile number and byte 2 the
version number of the profile.
NOTICE
This parameter is not visible via LCP.
9-70 Programming Set-up
Option: Function:
Select the set-up to be edited.
[0] Factory setup Uses default data. This option can be used
as a data source to return the other set-ups
to a known state.
[1] Set-up 1 Edits Set-up 1.
[2] Set-up 2 Edits Set-up 2.
[3] Set-up 3 Edits Set-up 3.
[4] Set-up 4 Edits Set-up 4.
[9] * Active Set-up Follows the active set-up selected in
0-10 Active Set-up.
This parameter is unique for LCP and fieldbus. See
0-11 Programming Set-up.
9-71 Profibus Save Data Values
Option: Function:
Parameter values changed via PROFIBUS are not
automatically stored in non-volatile memory.
Use this parameter to activate a function that
stores parameter values in the EEPROM non-
volatile memory, so changed parameter values
are retained at power-down.
[0] * Off Deactivates the non-volatile storage function.
[1] Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to
[0] Off when all parameter values have been
stored.
[2] Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to
[0] Off when all parameter values have been
stored.
9-72 ProfibusDriveReset
Option: Function:
[0] * No action
[1] Power-on
reset
Resets frequency converter upon power-up, as
for power-cycle.
[3] Comm
option
reset
Resets the PROFIBUS option only, useful after
changing certain settings in parameter group
9-**, for example, parameter 9-18 Node Address.
9-72 ProfibusDriveReset
Option: Function:
When reset, the frequency converter
disappears from the fieldbus, which may cause
a communication error from the master.
9-80 Defined Parameters (1)
Array [116]
No LCP access
Read only
Range: Function:
0* [0 - 9999 ] This parameter displays a list of all the defined
frequency converter parameters available for
PROFIBUS.
9-81 Defined Parameters (2)
Array [116]
No LCP access
Read only
Range: Function:
0* [0 - 9999 ] This parameter displays a list of all the defined
frequency converter parameters available for
PROFIBUS.
9-82 Defined Parameters (3)
Array [116]
No LCP access
Read only
Range: Function:
0* [0 - 9999 ] This parameter displays a list of all the defined
frequency converter parameters available for
PROFIBUS.
9-83 Defined Parameters (4)
Array [116]
No LCP access
Read only
Range: Function:
0* [0 - 9999 ] This parameter displays a list of all the defined
frequency converter parameters available for
PROFIBUS.
9-90 Changed Parameters (1)
Array [116]
No LCP access
Read only
Range: Function:
0* [0 - 9999 ] This parameter displays a list of all the
frequency converter parameters deviating from
default setting.
Parameters Programming Guide
40 Danfoss A/S © Rev. 05/2014 All rights reserved. MG37G102
66

Table of Contents

Other manuals for Danfoss vlt fcd 302

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt fcd 302 and is the answer not in the manual?

Danfoss vlt fcd 302 Specifications

General IconGeneral
BrandDanfoss
Modelvlt fcd 302
CategoryController
LanguageEnglish

Related product manuals