EasyManuals Logo

Danfoss VLT HVAC Basic Drive FC 101 Programming Guide

Danfoss VLT HVAC Basic Drive FC 101
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #38 background imageLoading...
Page #38 background image
3.2.7 1-5* Load Indep. Setting
Parameters for load-independent motor settings.
1-50 Motor Magnetisation at Zero Speed
Range: Function:
100
%*
[0 -
300 %
]
Use this parameter along with parameter 1-52 Min
Speed Normal Magnetising [Hz] to obtain a
dierent thermal load on the motor when running
at low speed.
Enter a value that is a percentage of the rated
magnetizing current. If the setting is too low, the
torque on the motor shaft may be reduced.
Magn. current
130BB780.10
Hz
Par.1-50
90%
Par.1-52
Illustration 3.2 Motor Magnetization
1-52 Min Speed Normal Magnetising [Hz]
Range: Function:
1 Hz* [0.1 - 10.0
Hz]
Set the required frequency for normal
magnetizing current.
Use this parameter along with
parameter 1-50 Motor Magnetisation at Zero
Speed. See Illustration 3.2.
1-55 U/f Characteristic - U
Array [6]
Range: Function:
Size related* [0 - 999
V]
Enter voltage at each frequency point
to form a U/f characteristic matching
the motor. Frequency points are
dened in parameter 1-56 U/f Charac-
teristic - F.
1-56 U/f Characteristic - F
Array[6]
Range: Function:
Size
related*
[ 0 -
400.0
Hz]
Enter frequency points to form a U/f charac-
teristic matching the motor. Voltage at each
point is dened in parameter 1-55 U/f Charac-
teristic - U.
Make a U/f characteristic based on 6 denable
voltages and frequencies, see Illustration 3.3.
Simplify U/f characteristics by merging 2 or
more points (voltages and frequencies). Set
the points at equal values.
1-56 U/f Characteristic - F
Array[6]
Range: Function:
Motor Voltage
Par 1-55 [x]
Output Frequency
Par 1-56 [x]
1-55[5]
1-55[4]
1-55[3]
1-55[2]
1-55[1]
1-55[0]
1-56
[0]
1-56
[1]
1-56
[2]
1-56
[3]
1-56
[4]
1-56
[5]
130BA166.10
Illustration 3.3 U/f Characteristic
3.2.8 1-6* Load Depen. Setting
Parameters for adjusting the load-dependent motor
settings.
1-62 Slip Compensation
Range: Function:
Size
related*
[-400 -
400 %]
Enter the % value for slip compensation
to compensate for tolerances in the
value of n
M,N
. Slip compensation is
calculated automatically, which is based
on the nominal motor speed n
M,N
.
1-63 Slip Compensation Time Constant
Range: Function:
0.1 s* [0.05 - 5 s] Enter the slip compensation reaction speed.
A high value results in slow reaction, and a
low value results in quick reaction. If low-
frequency resonance problems occur, use a
longer time setting.
1-64 Resonance Dampening
Range: Function:
100
%*
[0 -
500 %]
Enter the resonance damping value. Set
parameter 1-64 Resonance Dampening and
parameter 1-65 Resonance Dampening Time
Constant to help eliminate high-frequency
resonance problems. To reduce resonance
oscillation, increase the value of
parameter 1-64 Resonance Dampening.
1-65 Resonance Dampening Time Constant
Range: Function:
0.005 s* [0.001 -
0.050 s]
Set parameter 1-64 Resonance Dampening
and parameter 1-65 Resonance Dampening
Time Constant to help eliminate high-
frequency resonance problems. Enter the
time constant that provides the best
dampening.
Parameters
VLT
®
HVAC Basic Drive FC 101
36 Danfoss A/S © 04/2018 All rights reserved. MG18B502
33

Table of Contents

Other manuals for Danfoss VLT HVAC Basic Drive FC 101

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Basic Drive FC 101 and is the answer not in the manual?

Danfoss VLT HVAC Basic Drive FC 101 Specifications

General IconGeneral
BrandDanfoss
ModelVLT HVAC Basic Drive FC 101
CategoryDC Drives
LanguageEnglish

Related product manuals