What to do if Danfoss VLT HVAC Drive FC 102 show over current?
- AAaron DavisSep 19, 2025
If your Danfoss DC drive shows an over current error, it means the inverter peak current limit (approximately 200% of the rated current) is exceeded. You should remove power and check if the motor shaft can be turned. Also, check that the motor size matches the frequency converter and verify parameters 1-20 through 1-25 for correct motor data.