23-15 Reset Maintenance Word
Option: Function:
Set this parameter to
Do reset
[1] to reset the Maintenance Word in par.16-96
Maintenance Word
and reset the message displayed in the LCP. This parameter will change back to
Do not reset
[0]
when pressing OK.
[0] * Do not reset
[1] Do reset
NOTE!
When messages are reset - Maintenance Item, Action and Maintenance Date/Time are not cancelled. par.23-12
Maintenance Time
Base
is set to Disabled [0].
23-16 Maintenance Text
Range: Function:
0 N/A* [0 - 0 N/A] 6 individual texts (Maintenance Text 0...Maintenance Text 5) can be written for use in either par.
23-10
Maintenance Item
or par.23-11
Maintenance Action
.
The text is written according to the guidelines in par.0-37
Display Text 1
.
3.21.3 23-5* Energy Log
The adjustable frequency drive is continuously accumulating the consumption of the motor controlled, based on the actual power yielded by the adjustable
frequency drive.
These data can be used for an Energy Log function allowing the user to compare and structure the information about the energy consumption related
to time.
There are basically two functions:
- Data related to a pre-programmed period, defined by a set date and time for start
- Data related to a predefined period back in time, e.g., the last seven days within the pre-programmed period
For each of the above two functions, the data are stored in a number of counters allowing for selecting the time frame and a split on hours, days or
weeks.
The period/split (resolution) can be set in par.23-50
Energy Log Resolution
.
The data are based on the value registered by the kWh counter in the adjustable frequency drive. This counter value can be read in par.15-02
kWh
Counter
containing the accumulated value since the first power-up or latest reset of the counter (par.15-06
Reset kWh Counter
).
All data for the energy log are stored in counters which can be read from par.23-53
Energy Log
.
VLT
®
HVAC Drive Programming Guide 3 Parameter Description
MG.11.C6.22 - VLT
®
is a registered Danfoss trademark
3-219
3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Series and is the answer not in the manual?

Danfoss VLT HVAC Series Specifications

General IconGeneral
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Communication InterfacesProfibus, Ethernet
Cooling MethodForced convection
Ambient Temperature-10°C to +40°C
Enclosure RatingIP20, IP21, IP55
Output Voltage0 - 100% of supply voltage