EasyManua.ls Logo

Danfoss VLT MCD 600 - Pressure Sensor

Danfoss VLT MCD 600
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.7 Low Pressure
Cause
The pressure sensor connected to the smart card has activated low-pressure protection.
Troubleshooting
Check the following parameters:
- Parameter 30-1 Pressure Sensor Type.
- Parameter 30-3 Pressure at 4 mA.
- Parameter 30-4 Pressure at 20 mA.
- Parameter 32-4 Low Pressure Trip Level.
- Parameter 32-5 Low Pressure Start Delay.
- Parameter 32-6 Low Pressure Response Delay.
- Parameter 36-5 Low Pressure.
7.8 Low Water
Cause
The depth sensor connected to the smart card has activated depth protection.
Troubleshooting
Check the following parameters:
- Parameter 30-12 Depth Sensor Type.
- Parameter 30-14 Depth at 4 mA.
- Parameter 30-15 Depth at 20 mA.
- Parameter 34-1 Depth Trip Level.
- Parameter 34-2 Depth Reset Level.
- Parameter 34-3 Depth Start Relay.
- Parameter 36-9 Well Depth.
7.9 Pressure Sensor
Cause
The smart card has detected a fault with the pressure sensor.
Troubleshooting
Check the following parameters:
- Parameter 30-1 Pressure Sensor Type.
- Parameter 36-1 Pressure Sensor.
Trip Messages
Installation Guide | Pumping Smart Card
AN279052730268en-000102 / 175R1183 | 31
Danfoss A/S © 2018.10

Table of Contents

Other manuals for Danfoss VLT MCD 600

Related product manuals