Option
Function
Motor Set Select
Reverse Direction
Pump Clean
Table 141: 7-6 - Input B Trip
Option
Function
Selects when an input trip can occur.
Always Active
*
Operating Only
Run Only
Table 142: 7-7 - Input B Trip Delay
Range
Function
* 0 s
0:00–4:00 (minutes:seconds)
Sets a delay between the input activating and the soft starter tripping.
Table 143: 7-8 - Input B Initial Delay
Range
Function
* 0 s
00:00–30:00 (minutes:seconds)
Sets a delay before an input trip can occur.
The initial delay is counted from the time a start signal is received.
The state of the input is ignored until the initial delay has elapsed.
Table 144: 7-9 - Reset/Enable Logic
Option
Function
Selects whether the reset input (RESET, COM+) is normally open or normally closed.
*
Normally Closed
Normally Open
N O T I C E
If the reset input is active, the soft starter does not operate.
Table 145: 7-10 - Input A Name
Option
Function
Selects a message for the LCP to show when Input A is active.
The custom message can be loaded via the USB port.
*
Input A Trip
Low Pressure
High Pressure
Pump Fault
AQ262141844215en-000401 / 175R1174102 | Danfoss A/S © 2020.12
Programmable Parameters
VLT® Soft Starter MCD 600
Operating Guide

Table of Contents

Other manuals for Danfoss VLT MCD 600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT MCD 600 and is the answer not in the manual?

Danfoss VLT MCD 600 Specifications

General IconGeneral
BrandDanfoss
ModelVLT MCD 600
CategoryController
LanguageEnglish

Related product manuals