Table 141: 7-6 - Input B Trip
Selects when an input trip can occur.
Table 142: 7-7 - Input B Trip Delay
0:00–4:00 (minutes:seconds)
Sets a delay between the input activating and the soft starter tripping.
Table 143: 7-8 - Input B Initial Delay
00:00–30:00 (minutes:seconds)
Sets a delay before an input trip can occur.
The initial delay is counted from the time a start signal is received.
The state of the input is ignored until the initial delay has elapsed.
Table 144: 7-9 - Reset/Enable Logic
Selects whether the reset input (RESET, COM+) is normally open or normally closed.
N O T I C E
If the reset input is active, the soft starter does not operate.
Table 145: 7-10 - Input A Name
Selects a message for the LCP to show when Input A is active.
The custom message can be loaded via the USB port.
AQ262141844215en-000401 / 175R1174102 | Danfoss A/S © 2020.12
Programmable Parameters
VLT® Soft Starter MCD 600
Operating Guide