Table 73: 3-19 - Brake Current Limit-2
Sets the current limit for soft brake.
Table 74: 3-20 - Soft Brake Delay-2
Sets the time which the soft starter waits after a stop signal is received, before it begins to supply brak-
ing current to the motor. Set to allow time for K1 and K2 to switch.
10.8 Parameter Group 4-** Auto-Start/Stop
Table 75: 4-1 - Auto-Start/Stop Mode
Enable or disable auto-start/stop operation.
Table 76: 4-2 - Run Time
Sets the duration for the soft starter to run after a timer mode auto-start.
Table 77: 4-3 - Stopped Time
Sets the duration for the soft starter to remain stopped when operating in timer mode.
Table 78: 4-4 - Sunday Mode
Enables or disables auto-start/stop for Sunday.
Disables auto-start/stop control. Any times scheduled in parameter 4-5 Sunday Start Time or parameter
4-6 Sunday Stop Time are ignored.
Enables auto-start control. Any auto-stop times scheduled in parameter 4-6 Sunday Stop Time are ignor-
ed.
Enables auto-stop control. Any auto-start times scheduled in parameter 4-5 Sunday Start Time are ignor-
ed.
Enables auto-start and auto-stop control.
Table 79: 4-5 - Sunday Start Time
Sets the auto-start time for Sunday (24-hour format).
AQ262141844215en-000401 / 175R1174 | 89Danfoss A/S © 2020.12
Programmable Parameters
VLT® Soft Starter MCD 600
Operating Guide