Table 201: 12-21 - Location ID
Sets the soft starter's unique location ID.
10.17 Parameter Group 20-** Advanced
Table 202: 20-1 - Tracking Gain
Fine-tunes the behavior of the adaptive control algorithm.
Table 203: 20-2 - Pedestal Detect
Adjusts the behavior of the adaptive control algorithm for soft stop.
Table 204: 20-3 - Bypass Contactor Delay
Sets the soft starter to match the bypass contactor closing/opening time. Set according to the specifica-
tions of the bypass contactor used. If this time is too short, the soft starter will trip.
Table 205: 20-4 - Model Rating
The soft starter’s internal model reference, as shown on the silver label on the side of the unit. This parameter
is a read-only parameter. If the software is to be upgraded (SW version 3.0 and after), as part of applying the
upgrade firmware update, the MCD 600 requests the M/R code to be entered. This code is printed on the
product serial label as shown [1] below. This is only required to be entered once as part of the update proc-
ess. When entered, the parameter switches back to read-only If a wrong value by mistake has been entered,
this can re-activate the field by pressing [▵]/[▿] and cycling the control power. Once the code is re-entered, it
will again become read-only.
N O T I C E
This parameter can only be adjusted by authorized servicing agents.
Table 206: 20-5 - Screen Timeout
Sets the timeout for the menu to close automatically if no LCP activity is detected.