Table 95: 4-22 - Saturday Mode
Enables or disables auto-start/stop for Saturday.
Table 96: 4-23 - Saturday Start Time
Sets the auto-start time for Saturday (24-hour format).
Table 97: 4-24 - Saturday Stop Time
Sets the auto-stop time for Saturday (24-hour format).
10.9 Parameter Group 5-** Protection Levels
Table 98: 5-1 - Current Imbalance
Sets the trip point for current imbalance protection.
Table 99: 5-2 - Current Imbalance Delay
0:00–4:00 (minutes:seconds)
Slows the soft starter's response to current imbalance, avoiding trips due to momentary
fluctuations.
Table 100: 5-3 - Undercurrent
Sets the trip point for undercurrent protection as a percentage of motor full load current. Set to a level be-
tween the motor's normal working range and the motor's magnetizing (no load) current (typically 25–35% of
FLC). A setting of 0% disables undercurrent protection.
Table 101: 5-4 - Undercurrent Delay
00–4:00 (minutes:seconds)
Slows the soft starter's response to undercurrent, avoiding trips due to momentary fluctua-
tions.
Table 102: 5-5 - Overcurrent
Sets the trip point for overcurrent protection as a percentage of motor full load current.
AQ262141844215en-000401 / 175R117492 | Danfoss A/S © 2020.12
Programmable Parameters
VLT® Soft Starter MCD 600
Operating Guide