Table 87: 4-14 - Wednesday Start Time
Range
Function
*00:00
00:00–23:59
Sets the auto-start time for Wednesday (24-hour format).
Table 88: 4-15 - Wednesday Stop Time
Range
Function
*00:00
00:00–23:59
Sets the auto-stop time for Wednesday (24-hour format).
Table 89: 4-16 - Thursday Mode
Option
Function
Enables or disables auto-start/stop for Thursday.
*
Start/Stop Disable
Start Only Enable
Stop Only Enable
Start/Stop Enable
Table 90: 4-17 - Thursday Start Time
Range
Function
*00:00
00:00–23:59
Sets the auto-start time for Thursday (24-hour format).
Table 91: 4-18 - Thursday Stop Time
Range
Function
*00:00
00:00–23:59
Sets the auto-stop time for Thursday (24-hour format).
Table 92: 4-19 - Friday Mode
Option
Function
Enables or disables auto-start/stop for Friday.
*
Start/Stop Disable
Start Only Enable
Stop Only Enable
Start/Stop Enable
Table 93: 4-20 - Friday Start Time
Range
Function
*00:00
00:00–23:59
Sets the auto-start time for Friday (24-hour format).
Table 94: 4-21 - Friday Stop Time
Range
Function
*00:00
00:00–23:59
Sets the auto-stop time for Friday (24-hour format).
AQ262141844215en-000401 / 175R1174 | 91Danfoss A/S © 2020.12
Programmable Parameters
VLT® Soft Starter MCD 600
Operating Guide

Table of Contents

Other manuals for Danfoss VLT MCD 600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT MCD 600 and is the answer not in the manual?

Danfoss VLT MCD 600 Specifications

General IconGeneral
BrandDanfoss
ModelVLT MCD 600
CategoryController
LanguageEnglish

Related product manuals