Table 162: 10-2 - Temperature Scale
Selects whether the soft starter shows temperatures in degrees Celsius or Fahrenheit.
Table 163: 10-3 - Graph Timebase
Sets the graph time scale.
The graph replaces the old data with new data progressively.
Table 164: 10-4 - Graph Maximum Adjustment
Adjusts the upper limit of the performance graph.
Table 165: 10-5 - Graph Minimum Adjustment
Adjusts the lower limit of the performance graph.
Table 166: 10-6 - Current Calibration
Calibrates the soft starter's current monitoring circuits to match an external current metering device. Use the
following formula to determine the necessary adjustment:
Calibration % =
Currentshownonsoftstarterdisplay
Currentmeasuredbyexternaldevice
Table 167: 10-7 - Adjustment Lock
Selects whether the LCP allows parameters to be changed via the Main Menu.
Allows altering of parameter values in the Main Menu.