Model
Nominal rating [A]
@480 V AC
Fault current rat-
ing [kA]
Fuse rating [A]
Fuse class
Circuit breaker rating [A]
MCD6-0287
352
400
Any (J, T, K-1, RK1, RK5)
HLD3400 (400)
SFLA36AT0600 (600)
UTS400H-xxU-400 (400)
MCD6-0323B
397
450
HLD3400 (400)
SFLA36AT0600 (600)
UTS400H-xxU-400 (400)
MCD6-0410B
410
450
HLD3600 (600)
SFLA36AT0600 (600)
UTS600H-xxU-600 (600)
MCD6-0527B
550
600
HLD3600 (600)
SFLA36AT0600 (600)
UTS800H-xxU-800 (800)
MCD6-0579B
580
600
HLD3600 (600)
SGLA36AT0600 (600)
UTS800H-NGO-800 (800)