EasyManua.ls Logo

Danfoss VLT MCD 600 - Page 77

Danfoss VLT MCD 600
140 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
N O T I C E
For duty/standby applications, set parameter 6-17 Motor Overtemperature to Log Only and install temperature protection for each
motor.
To use the secondary motor set, set a programmable input to Motor Set Select. The input must be closed when a start command is
given (see parameter 7-1 Input A Function and parameter 7-5 Input B Function). The soft starter checks which motor set to use at start
and uses that motor set for the entire start/stop cycle.
The soft starter uses the secondary motor settings to control a start when instructed via a programmable input (see parameter 7-1
Input A Function and parameter 7-5 Input B Function).
AQ262141844215en-000401 / 175R1174 | 73Danfoss A/S © 2020.12
Operation
VLT® Soft Starter MCD 600
Operating Guide

Table of Contents

Other manuals for Danfoss VLT MCD 600

Related product manuals